How to make shaft learning for 2 floor elevator with Nice 9000 controller
2026-04-13 14:16:23

First, observe the FA-05 parameter value. Additionally, all other self-learning conditions must be correctly met:

 

A. The normally open and normally closed positions of the leveling sensor switch and the corresponding F5-01 parameter value settings;

 

B. The installation and signal of the up/down deceleration (speed change) switch are normal;

 

C. The total number of floors and the elevator's rated speed parameter values are correctly set;

 

D. When learning on the ground floor: F4-01=01 (This parameter value will change; it will display the floor number the elevator is on).

 

I. Mini Control Cabinet: 01.005FA-05<02.00

 

① When the elevator reaches the bottom floor, it will perform shaft self-learning. Upon reaching the top floor, it will report fault E35-114.

 

Do not rush to clear the fault;

 

② Switch the control cabinet back to inspection (or maintenance) mode;

 

③ Modify parameter F3-29. Note that the unit is mm, and the parameter value should be the length:

 

For example, if the length of the magnetic plate (or magnetic strip) is 10 cm, then F3-29 = 100;

 

④ After completing the above steps, clear fault E35-114;

 

⑤ Finally, de-energize for a longer period before re-energizing. The elevator can then run at high speed.

 

II. Mini Control Cabinet: FA-05=02.00

 

① The elevator will run to the bottom floor and perform shaft self-learning. Upon reaching the top floor, it will report fault E35-114.

 

Do not rush to clear the fault:

 

② Re-switch the control cabinet to inspection (or maintenance) mode;

 

③ Modify parameter A1-17. Note that the unit is mm, and the parameter value should be the length:

 

For example, if the length of the magnetic plate (or magnetic strip) is 10 cm, then A1-17=100;

 

④ After completing the above steps, clear fault E35-114;

 

⑤ Finally, de-energize for a longer period before re-energizing. The elevator can then run at high speed.

 

Note: If leveling occurs after learning, either move the magnetic plate (or magnetic strip) up or down, or fine-tune the leveling using parameter Fr-00=1.

 

III. Glory Cabinet: 10.005FA-05<11.00

 

① When the elevator reaches the bottom floor, it will perform shaft self-learning. Upon reaching the top floor, it will report fault E35-114.

 

Do not rush to clear the fault;

 

② Switch the control cabinet back to inspection (or maintenance) mode;

 

③ Modify parameter F3-29. Note that the unit is mm, and the parameter value should be the length:

 

For example, if the length of the magnetic plate (or magnetic strip) is 10 cm, then F3-29 = 100;

 

④ After completing the above steps, clear fault E35-114;

 

⑤ Finally, de-energize for a longer period before re-energizing. At this time, the elevator can run at high speed.

 

IV. Glory Cabinet: FA-05=11.00

 

① When the elevator reaches the bottom floor, it will perform shaft self-learning. Upon reaching the top floor, it will report fault E35-114.

 

Do not rush to clear the fault;

 

② Switch the control cabinet back to inspection (or maintenance) mode;

 

③ Modify parameter A1-17. Note that the unit is mm, and the parameter value should be the length:

 

For example, if the length of the magnetic plate (or magnetic strip) is 10 cm, then A1-17=100;

 

④ After completing the above steps, clear fault E35-114;

 

⑤ Finally, power off for a longer period before powering on. At this time, the elevator can run at high speed.

 

Note: If leveling occurs after learning: either move the magnetic plate (or magnetic strip) up or down, or fine-tune the leveling using parameter Fr-00=1.